  • 5.14.6. When installing equipment in rooms, it is necessary to consider the height of reach by wheelchair users (calculated from floor or ground surface) and regulated as follows

    doc7p alibabava40tencuop 21-09-2009 113 25   Download

  • 5.9.9. It is not advisable to arrange door sill or nosing in the interior side of door, in case the clearance space is less than 800 mm. Note: It is only permissible to arrange door sill and nosing in the interior side of door in case the clearance space exceeds 800 mm, and the door sill or nosing does not exceed 50 mm. 5.9.10. As for pulling door, sliding door, accordion door, the clearance space regarding each door type is shown in table 4 and table 5. a) Pulling door: Regulation on clearance space for wheelchair moving is indicated in fig 32....

    doc11p alibabava40tencuop 21-09-2009 119 21   Download

  • 5.5.3. Where in two sides of corridor there is wall edge, then the clearance width must be in accordance with regulation in clause 5.5.1. 5.5.4. Handrails in two sides of corridor must be at an elevation of 900mm. Rotating angle at deviation points is preferably arched wall face or right angled wall face. Where there is difference in elevation at the extremity of corridor and the end of corridor with floor surface or ground surface, it must be balustrade, shielding plate or shielding edge, and there is a need for installation of safety signpost. ...

    doc20p alibabava40tencuop 21-09-2009 127 41   Download