CHAPTER 8 : EXPANSION VALVE

Lecturer : ThS.Nguyễn Duy Tuệ Lecturer : ThS Nguyễn Duy Tuệ

1

12/2015

Chapter 8: Expansioln valve ThS.Nguyễn Duy Tuệ

OBJECTIVES

In this chapter, student can : In this chapter student can :

- Understand operation priciple of some kind

of expansion valves

- Choose the thermal expansion which is

suitable for requirements

12/2015

2

Chapter 8: Expansioln valve ThS.Nguyễn Duy Tuệ

REFERENCES

[1]. Refrigeration and Air-Conditioning - A. R. [1] Refrigeration and Air Conditioning A R Trott and T. Welch [ ] [2]. Danfoss expansion valve catalogue

p

g

12/2015

3

Chapter 8: Expansioln valve ThS.Nguyễn Duy Tuệ

CONTENT

INTRODUCTION

THERMOSTATIC EXPANSION VALVE

ELECTRONIC EXPANSION VALVE

LOW PRESSURE FLOAT VALVE

HIGH PRESSURE FLOAT VALVE HIGH PRESSURE FLOAT VALVE

12/2015

Chapter 8: Expansioln valve ThS.Nguyễn Duy Tuệ

4

CONTENT

CAPILLARY TUBES AND RESTRICTORS

OTHER LEVEL CONTROL

CHOOSING THERMOSTATIC EXPANSION VALVE

12/2015

Chapter 8: Expansioln valve ThS.Nguyễn Duy Tuệ

5

INTRODUCTION

l th fl - The purpose of f i t t f f

the expansion valve is to control the flow of refrigerant from the high-pressure th hi h condensing side of the system into the low-pressure evaporator. evaporator

- In most cases,

g ,

the pressure reduction is achieved through a variable flow orifice, either modulating or two-position. Expansion valves may be classified according to the method of control.

12/2015

Chapter 8: Expansioln valve ThS.Nguyễn Duy Tuệ

6

THERMOSTATIC S O EXPANSION VALVE

1. Reason why we have to use thermostatic

l expansion valve ? ?

there is no risk of there is no risk of

p g

region. The amount of superheat

i Direct expansion circuits must be designed liquid liquid and installed so that and installed so that refrigerant returning to the compressor. To ensure this state, heat exchange surface in the evaporator , the dry saturated gas into the is used to heat superheat is usually of the order of 5 K. -> Useful superheat

12/2015

Chapter 8: Expansioln valve ThS.Nguyễn Duy Tuệ

7

THERMOSTATIC S O EXPANSION VALVE

2. Operation principle : t ti Th b i th h i l

- The basic thermostatic expansion valve has a detector and power element, charged with the same refrigerant as in the circuit. refrigerant as in the circuit

g p g p y

- The pressure ps generated in the phial by the superheated gas passes through the capillary tube p to the top of the diaphragm. An adjustable spring provides the balance of ps ;pe at the diaphragm, and the valve stem is attached at the centre.

- Should the superheat fall for any reason, there

will be a risk of liquid reaching the compressor. will be a risk of liquid reaching the compressor

12/2015

Chapter 8: Expansioln valve ThS.Nguyễn Duy Tuệ

8

THERMOSTATIC S O EXPANSION VALVE

ps>pe+pspring : Valve open pspring ps pe ps

12/2015

Chapter 8: Expansioln valve ThS.Nguyễn Duy Tuệ

9

THERMOSTATIC S O EXPANSION VALVE

12/2015

Chapter 8: Expansioln valve ThS.Nguyễn Duy Tuệ

10

THERMOSTATIC S O EXPANSION VALVE

t ill If f i d th ill b li

increases, the load on the evaporator refrigerant will evaporate earlier and there will be t more superheat at the phial position. Then p s will increase and open the valve wider to meet the new increase and open the valve wider to meet the new demand.

12/2015

Chapter 8: Expansioln valve ThS.Nguyễn Duy Tuệ

11

THERMOSTATIC S O EXPANSION VALVE

http://www.ra.danfoss.com/TechnicalInfo/Approvals/Files /RAPIDFiles/01/Asset/TE55-Ver/TE55-Ver.10.03.25-.02- 2D-L.swf 2D L swf

12/2015

Chapter 8: Expansioln valve ThS.Nguyễn Duy Tuệ

12

THERMOSTATIC S O EXPANSION VALVE

12/2015

Chapter 8: Expansioln valve ThS.Nguyễn Duy Tuệ

13

THERMOSTATIC S O EXPANSION VALVE

http://www.ra.danfoss.com/TechnicalInfo/Approvals/Files /RAPIDFiles/01/Asset/TE55-Ver/TE55-Ver.10.03.25-.02- 2D-L.swf 2D L swf

12/2015

Chapter 8: Expansioln valve ThS.Nguyễn Duy Tuệ

14

THERMOSTATIC S O EXPANSION VALVE

12/2015

Chapter 8: Expansioln valve ThS.Nguyễn Duy Tuệ

15

THERMOSTATIC S O EXPANSION VALVE

Dependence of ts-ps at the bult

12/2015

Chapter 8: Expansioln valve ThS.Nguyễn Duy Tuệ

16

THERMOSTATIC S O EXPANSION VALVE

t f i ithi i d b it h

The power element can be limit charged so that all the refrigerant within it has vaporized by a th ll predetermined temperature (commonly 0°C). Above this point, the pressure within it will cease of follow this point the pressure within it will cease of follow the boiling point curve but will follow the gas laws as shown in :

-> the valve will remain closed.

12/2015

Chapter 8: Expansioln valve ThS.Nguyễn Duy Tuệ

17

THERMOSTATIC S O EXPANSION VALVE

Detector pressure for limit charged valve:

12/2015

Chapter 8: Expansioln valve ThS.Nguyễn Duy Tuệ

18

THERMOSTATIC S O EXPANSION VALVE

t t fi ti hi h t

- This is done to limit the evaporator pressure when first starting a warm system, which might i ht h overload the drive motor. This is termed limit charging or maximum operating pressure -> MOP charging or maximum operating pressure -> MOP valve

- Such valves must be installed so that the phial is p

the coldest part.

12/2015

Chapter 8: Expansioln valve ThS.Nguyễn Duy Tuệ

19

THERMOSTATIC S O EXPANSION VALVE

When soldering, we have to wrap the valve’s

body by a wet cloth b d b th t l

12/2015

Chapter 8: Expansioln valve ThS.Nguyễn Duy Tuệ

20

THERMOSTATIC S O EXPANSION VALVE

i l i li th Th

small

drops p can g coil y j

3. External equalizer : - The simple thermostatic expansion valve relies ti t l the diaphragm being on the pressure under approximately the same as that at the coil outlet, approximately the same as that at the coil outlet and be pressure accommodated by adjustments to the spring setting. g - If evaportor have high pressure drop due to distributor, large coil, there will be the large pressure difference between inlet and outlet coil -> Have equalizing connection

12/2015

Chapter 8: Expansioln valve ThS.Nguyễn Duy Tuệ

21

THERMOSTATIC S O EXPANSION VALVE

Thermostatic expansion valve with external equalizer li

12/2015

Chapter 8: Expansioln valve ThS.Nguyễn Duy Tuệ

22

THERMOSTATIC S O EXPANSION VALVE

4. What is the hunting of expansion valve : Excessive E hunting h ti the th of f i thermostatic th ti t

expansion valve means that:

- The evaporator surface has an irregular - The evaporator surface has an irregular refrigerant feed with a resulting slight loss of heat transfer effectiveness.

- a time lag between the change of valve

position and the effect at the evaporator outlet

- Over-sized valves and incorrect phial position

can also give rise to hunting.

12/2015

Chapter 8: Expansioln valve ThS.Nguyễn Duy Tuệ

23

THERMOSTATIC S O EXPANSION VALVE

+ Solutions: l Th hi t d th ld h h l

- The phial should always he located on the l horizontal outlet, as close to the evaporator as possible and not on the underside of the pipe. possible and not on the underside of the pipe

- Electronic expansion valves are now becoming

increasingly popular for many applications. g y p p y pp

12/2015

Chapter 8: Expansioln valve ThS.Nguyễn Duy Tuệ

24

THERMOSTATIC S O EXPANSION VALVE

12/2015

Chapter 8: Expansioln valve ThS.Nguyễn Duy Tuệ

25

THERMOSTATIC S O EXPANSION VALVE

12/2015

Chapter 8: Expansioln valve ThS.Nguyễn Duy Tuệ

26

THERMOSTATIC S O EXPANSION VALVE

12/2015

Chapter 8: Expansioln valve ThS.Nguyễn Duy Tuệ

27

THERMOSTATIC S O EXPANSION VALVE

12/2015

Chapter 8: Expansioln valve ThS.Nguyễn Duy Tuệ

28

THERMOSTATIC S O EXPANSION VALVE

+ Installation diagram: need solenoide valve

before thermostatic expansion valve before thermostatic expansion valve http://refrigerationandairconditioning.danfoss.us/kno wledge center/multimedia/refrigeration system wledge-center/multimedia/refrigeration-system- overview/

12/2015

Chapter 8: Expansioln valve ThS.Nguyễn Duy Tuệ

29

THERMOSTATIC S O EXPANSION VALVE

12/2015

Chapter 8: Expansioln valve ThS.Nguyễn Duy Tuệ

30

ELECTRONIC S O EXPANSION VALVE

1. Benefits of electronic expansion valve:

l i t ff fi l

The electronic expansion valve offers a finer Th i degree of control and system protection. The benefits can be summarized as: benefits can be summarized as:

capacities .

- Precise flow control over a wide range of p - Rapid response to load changes . - Better control at low superheats so that less evaporator surface is required for superheat. More surface for evaporation results in higher evaporating temperature and better efficiency. temperature and better efficiency

12/2015

Chapter 8: Expansioln valve ThS.Nguyễn Duy Tuệ

31

ELECTRONIC S O EXPANSION VALVE

ibilit ff t t l i

- Electrical connection between components offers greater flexibility in system layout, which is hi h i t fl important for compact systems.

- The valve can close when the system shuts - The valve can close when the system shuts down, which eliminates the need for an additional shut off solenoid valve.

12/2015

Chapter 8: Expansioln valve ThS.Nguyễn Duy Tuệ

32

ELECTRONIC S O EXPANSION VALVE

With l th ifi t l i i

2. Kinds of electronic expansion valve : - With electronic expansion valve, the orifice size is varied by : a stepper motor, and a pulse width modulated (PWM) type. width modulated (PWM) type

- In each case a controller

p

is used in conjunction with the valve. The controller is pre-confi j the refrigerant and valve type and it gured for receives the information from sensors, for example, pressure and temperature at the evaporator outlet. This enables the superheat to be determined. The output signal to the valve initiates the orifice to the valve initiates the orifice output signal adjustment.

12/2015

Chapter 8: Expansioln valve ThS.Nguyễn Duy Tuệ

33

ELECTRONIC S O EXPANSION VALVE

2. Kinds of electronic expansion valve : - With electronic expansion valve, the orifice With electronic expansion valve the orifice size is varied by : a stepper motor, and a pulse width modulated (PWM) type. width modulated (PWM) type.

- In each case a controller

t th d t tl t t

is used in conjunction with the valve. The controller is pre-confi gured for the refrigerant and valve type and it receives the information from sensors, for example, pressure and temperature at the evaporator outlet. t This enables the superheat to be determined. The to the valve initiates the orifice output signal to the valve initiates the orifice output signal adjustment.

12/2015

Chapter 8: Expansioln valve ThS.Nguyễn Duy Tuệ

34

ELECTRONIC S O EXPANSION VALVE

+ Installation diagram for electronic expansion

valve : valve :

12/2015

Chapter 8: Expansioln valve ThS.Nguyễn Duy Tuệ

35

ELECTRONIC S O EXPANSION VALVE

http://www.ra.danfoss.com/TechnicalInfo/Approvals/Files/RAPIDFiles/01/ Asset/ETS6-Ver/ETS6-Ver.20.08.12-.02-2D-L.swf

12/2015

36

Chapter 8: Expansioln valve ThS.Nguyễn Duy Tuệ

ELECTRONIC S O EXPANSION VALVE

12/2015

37

Chapter 8: Expansioln valve ThS.Nguyễn Duy Tuệ

ELECTRONIC S O EXPANSION VALVE

12/2015

38

Chapter 8: Expansioln valve ThS.Nguyễn Duy Tuệ

ELECTRONIC S O EXPANSION VALVE

12/2015

39

Chapter 8: Expansioln valve ThS.Nguyễn Duy Tuệ

ELECTRONIC S O EXPANSION VALVE

l th In the case of hi b t ti the PWM valve it i d l i

is the relationship between the opening and closing which hi h determines the capacity of the valve. The valve is either open or closed and each time interval of a few either open or closed and each time interval of a few seconds will include an opening period depending on the signal. g

12/2015

Chapter 8: Expansioln valve ThS.Nguyễn Duy Tuệ

40

ELECTRONIC S O EXPANSION VALVE

http://www.ra.danfoss.com/TechnicalInfo/Approvals/ Files/RAPIDFiles/01/Asset/AKV10-Ver/AKV10- Files/RAPIDFiles/01/Asset/AKV10-Ver/AKV10- Ver.10.01.27-.02-2D-L.swf

12/2015

Chapter 8: Expansioln valve ThS.Nguyễn Duy Tuệ

41

ELECTRONIC S O EXPANSION VALVE

12/2015

Chapter 8: Expansioln valve ThS.Nguyễn Duy Tuệ

42

ELECTRONIC S O EXPANSION VALVE

12/2015

Chapter 8: Expansioln valve ThS.Nguyễn Duy Tuệ

43

ELECTRONIC S O EXPANSION VALVE

12/2015

Chapter 8: Expansioln valve ThS.Nguyễn Duy Tuệ

44

ELECTRONIC S O EXPANSION VALVE

or partial condition

i hi h h

temperature,

p p

floating load Under condensing pressure, which happens at low l t d the condensing pressure ambient decreases. Thermostatic expansion valves tend to decreases Thermostatic expansion valves tend to hunt, but systems with electronic components operate at partial y load in exactly the same and stable manner as at full load.

12/2015

Chapter 8: Expansioln valve ThS.Nguyễn Duy Tuệ

45

LOW PRESSURE FLOAT VALVE

O

1. Description : - Flooded evaporators require a constant liquid Flooded evaporators require a constant liquid level, so that the tubes remain wetted. A simple float valve suffices (applied), but must be located with the valve suffices (applied), but must be located with the float outside the evaporator shell

in the mechanism. The float b h t f t

- Since the surface of the boiling liquid is agitated (stir) and the constant movement would cause is excessive wear therefore contained within a separate chamber, th ithi d i coupled with balance lines to the shell

12/2015

Chapter 8: Expansioln valve ThS.Nguyễn Duy Tuệ

46

LOW PRESSURE FLOAT VALVE

O

2. Figure of low pressure float valve:

12/2015

Chapter 8: Expansioln valve ThS.Nguyễn Duy Tuệ

47

LOW PRESSURE FLOAT VALVE

O

p p

- Such a valve is a metering device and may not provide positive shut-off when the compressor is not provide positive shut-off when the compressor is stopped. Under these circumstances, refrigerant will continue to leak into the evaporator until pressures have equalized, and the liquid level might rise too close to the suction outlet. To provide this shut-off, a solenoid valve is needed in the liquid line. d d i h li id li id l l i

- Since the low-pressure float needs a solenoid valve for tight closure, this valve can be used as an valve for tight closure this valve can be used as an on–off control in conjunction with a pre-set orifice and controlled by a float switch and controlled by a float switch

12/2015

Chapter 8: Expansioln valve ThS.Nguyễn Duy Tuệ

48

LOW PRESSURE FLOAT VALVE

O

+ Figure of float switch :

12/2015

Chapter 8: Expansioln valve ThS.Nguyễn Duy Tuệ

49

HIGH PRESSURE FLOAT VALVE

O

p

1. Description : A float valve can be fitted which will pass any A float valve can be fitted which will pass any to the drained liquid from the condenser direct evaporator. The action is the same as that of a is at condenser steam trap. The float chamber pressure and the control is termed a high-pressure flfloat

12/2015

Chapter 8: Expansioln valve ThS.Nguyễn Duy Tuệ

50

CẤP DỊCH BẰNG VAN PHAO U C O KIỂU CAO ÁP

2. Installation diagram:

12/2015

Chapter 8: Expansioln valve ThS.Nguyễn Duy Tuệ

51

HIGH PRESSURE FLOAT VALVE

O

In this diagram, the first upper coil superheat the vapour, the second one boil off the remaining the second one boil off the remaining the vapour liquid

12/2015

Chapter 8: Expansioln valve ThS.Nguyễn Duy Tuệ

52

CAPILLARY TUBES AND C O S RESTRICTORS

S

g y ,

The variable orifice of the expansion valve can be replaced, in small systems, by a long thin tube. be replaced in small systems by a long thin tube This is a non-modulating device and has certain limitations, but will give reasonably effective control over a wide range of conditions if correctly selected

12/2015

Chapter 8: Expansioln valve ThS.Nguyễn Duy Tuệ

53

CAPILLARY TUBES AND C O S RESTRICTORS

S

+ Capillary adjustment :

12/2015

Chapter 8: Expansioln valve ThS.Nguyễn Duy Tuệ

54

CAPILLARY TUBES AND C O S RESTRICTORS

S

- Tube bores of 0.8–2 mm with lengths of 1–4 m are common. The capillary tube is only fitted on are common The capillary tube is only fitted on factory-built and tested equipment, with exact refrigerant charges. g

g - Mass flow is a function of pressure difference

and the degree of liquid subcooling on entry.

ill Th b i d l l i

- The capillary tube is used almost exclusively l in small air conditioning systems and is self Increasing Increasing regulating within certain parameters. regulating within certain parameters ambient temperature -> increasing load and the condensing pressure rise more refrigerant flow. condensing pressure rise->more refrigerant flow.

12/2015

Chapter 8: Expansioln valve ThS.Nguyễn Duy Tuệ

55

CAPILLARY TUBES AND C O S RESTRICTORS

S

- Tube bores of 0.8–2 mm with lengths of 1–4 m are common. The capillary tube is only fitted on are common The capillary tube is only fitted on factory-built and tested equipment, with exact refrigerant charges. g

g - Mass flow is a function of pressure difference

and the degree of liquid subcooling on entry.

ill Th b i d l l i

- The capillary tube is used almost exclusively l in small air conditioning systems and is self Increasing Increasing regulating within certain parameters. regulating within certain parameters ambient temperature -> increasing load and the condensing pressure rise more refrigerant flow. condensing pressure rise->more refrigerant flow.

12/2015

Chapter 8: Expansioln valve ThS.Nguyễn Duy Tuệ

56

CAPILLARY TUBES AND C O S RESTRICTORS

S

Figure shows how the device is applied in a

reversible air conditioner. reversible air conditioner

12/2015

Chapter 8: Expansioln valve ThS.Nguyễn Duy Tuệ

57

OTHER LEVEL CONTROLLS

is placed at - If a small heater element

the required liquid level of a flooded evaporator, required liquid level of a flooded evaporator together with a heat-sensing element, then the latter will detect a greater temperature if liquid refrigerant will detect a greater temperature if liquid refrigerant is not present. This signal can be used to operate a solenoid valve.

h d b th l d t t t l

- The thermostatic or electronic expansion valve can also be used to maintain a liquid level. The phial and a heater element are both clamped to a bulb at b lb t the required liquid level. If liquid is not present, the heater warms the phial to a superheat condition and heater warms the phial to a superheat condition and the valve opens to admit more liquid.

12/2015

Chapter 8: Expansioln valve ThS.Nguyễn Duy Tuệ

58

OTHER LEVEL CONTROLLS

12/2015

Chapter 8: Expansioln valve ThS.Nguyễn Duy Tuệ

59

CHOOSING THERMOSTATIC S O EXPANSION VALE

We have to follow manufacturer catalogue for is valve. Following this valve is Following this

expansion choosing expansion choosing Danfoss’s catalogue:

12/2015

Chapter 8: Expansioln valve ThS.Nguyễn Duy Tuệ

60

CHOOSING THERMOSTATIC S O EXPANSION VALE

12/2015

Chapter 8: Expansioln valve ThS.Nguyễn Duy Tuệ

61

CHOOSING THERMOSTATIC S O EXPANSION VALE

12/2015

Chapter 8: Expansioln valve ThS.Nguyễn Duy Tuệ

62

CHOOSING THERMOSTATIC S O EXPANSION VALE

+ Lưu ý : Trong ví dụ trên ta chưa kể đến hệ số hiệu chỉnh do độ quá lạnh của môi chất trước khi hiệu chỉnh do độ quá lạnh của môi chất trước khi vào VTL. Độ quá lạnh lỏng càng lớn thì NSL tăng do sự hóa hơi đột ngột sau van giảm gộ ự g ộ

12/2015

Chapter 8: Expansioln valve ThS.Nguyễn Duy Tuệ

63

CHOOSING THERMOSTATIC S O EXPANSION VALE

12/2015

Chapter 8: Expansioln valve ThS.Nguyễn Duy Tuệ

64